The minimum cross-section needed to stay within the allowable voltage drop.

Published by SolucionesAhora.com How we verify

Calculator inputs

Material

System

Results

Enter your values and press “Calculate” to see the result.

Free, no sign-up! What if you could do this without a calculator? A five-minute game with challenges, lives and points. It clicks even when you cannot be bothered.

In short

What it calculates
The minimum cross-section needed to stay within the allowable voltage drop.
Formula used
S = factor × ρ × L × I ÷ allowable ΔV
Example
40 m of copper carrying 20 A at 230 V with a 3% maximum drop:

Cable size calculator

This is the inverse of the voltage drop calculation: you set the maximum loss you accept and get the minimum cross-section that meets it.

The answer is rounded up to the next standard commercial size.

How it works

The cross-section is isolated from the voltage drop formula and compared against the standard commercial range from 1.5 to 240 mm².

Formula

S = factor × ρ × L × I ÷ allowable ΔV

factor = 2 single phase, √3 three phase

Commercial sizes: 1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 mm²

Worked example

40 m of copper carrying 20 A at 230 V with a 3% maximum drop:

Allowable ΔV = 6.9 V
S = 2 × 0.0175 × 40 × 20 ÷ 6.9 = 4.06 mm²

Commercial size: 6 mm²

Explanation

Current capacity is not the only criterion

Sizing by maximum current stops the cable overheating, but does not guarantee the voltage arrives properly at the end of a long run. In installations of any length, the voltage drop criterion usually demands a larger cross-section than the heating one. Check both and take the more restrictive.

Why you always round up

Commercial cross-sections come in a standard series: 1.5, 2.5, 4, 6, 10 and so on. If the calculation calls for 3.7 square millimetres, you install 4. Never down, because an undersized conductor does not fail on day one: it degrades, its resistance rises and it becomes a fire risk.

What reduces cable capacity

Grouping several circuits in the same conduit, high ambient temperature, running under thermal insulation or buried without ventilation. Regulatory tables apply correction factors for each of those conditions, and omitting them is the commonest error when sizing on your own.

This does not replace an electrician

An electrical installation must comply with the regulations in force in your country and, in most cases, be carried out and certified by a licensed professional. This calculation is for orientation, not for signing off a project.

Frequently asked questions

Is this criterion enough on its own?

No. The cross-section must also satisfy the conductor’s current carrying capacity for its insulation and installation method, as set by national regulations.

Why round up?

Because only standard commercial sizes exist, and choosing the smaller one would breach the drop limit.

Is calculating by maximum current enough?

No. Over long runs, the voltage drop criterion usually demands a larger cross-section. Check both and apply the more restrictive.

Why round up?

Because commercial cross-sections form a fixed series and an undersized conductor degrades over time until it becomes a hazard.

Need to calculate something else?

These tools are often used alongside this calculator.

Voltage drop

Voltage lost along a conductor given its length, cross-section and material.

Ohm’s law

Enter two of voltage, current or resistance and get the third.

Electrical power

Active and apparent power for single and three phase installations.

Electricity use

What an appliance costs per month and per year based on hours of use.