Voltage drop calculator
Voltage lost along a conductor given its length, cross-section and material.
Calculator inputs
Results
Enter your values and press “Calculate” to see the result.
In short
- What it calculates
- Voltage lost along a conductor given its length, cross-section and material.
- Formula used
Single phase: ΔV = 2 × ρ × L × I ÷ S- Example
- 50 m of 2.5 mm² copper cable carrying 16 A at 230 V:
Voltage drop calculator
Every conductor has resistance, so the voltage reaching the load is lower than at the source. Over long runs that loss can stop a motor from starting.
How it works
The resistivity of the material is applied to the length and cross-section of the cable, multiplied by the current. The factor differs between single phase (out and back) and three phase.
Formula
Single phase: ΔV = 2 × ρ × L × I ÷ S
Three phase: ΔV = √3 × ρ × L × I ÷ S
ρ copper = 0.0175 Ω·mm²/m
ρ aluminium = 0.028 Ω·mm²/m
Worked example
50 m of 2.5 mm² copper cable carrying 16 A at 230 V:
ΔV = 2 × 0.0175 × 50 × 16 ÷ 2.5 = 11.2 V
Drop: 4.87%
That exceeds the 3% usually recommended for lighting.
Explanation
A long cable loses voltage along the way
Every conductor has resistance, and that resistance consumes part of the voltage as heat. Over a short run it is negligible, but over a hundred metres to a workshop, a well or a garden shed, the voltage arriving can be considerably lower than at the source.
The usual limits
Regulations typically allow around three per cent drop on lighting circuits and five per cent on power circuits, measured from the board. Exceeding them is not merely a formality: motors lose torque, lamps give less light and the whole system dissipates energy without doing useful work.
How to reduce it
Increasing conductor cross-section is the most direct route. Shortening the run, splitting the load across several circuits or raising the distribution voltage also work. On long installations it is usually cheaper to lay thicker cable from the start than to redo the installation later.
Low voltage direct current
In photovoltaic or twelve-volt installations the problem is worse: at equal power the current is much higher and the percentage drop soars. There, cable cross-section stops being a detail and becomes the main design factor.
Frequently asked questions
What drop is acceptable?
As a general guide, 3% for lighting and 5% for other uses, though every country has its own regulations.
How do I reduce it?
By increasing the cable cross-section or shortening the run. Doubling the section halves the drop.
What voltage drop is acceptable?
Usually around three per cent on lighting and five per cent on power circuits, though the exact figure depends on the applicable regulations.
How do I reduce voltage drop?
By increasing conductor cross-section, shortening the run, splitting the load across circuits or raising the distribution voltage.
Need to calculate something else?
These tools are often used alongside this calculator.
Cable size
The minimum cross-section needed to stay within the allowable voltage drop.
Ohm’s law
Enter two of voltage, current or resistance and get the third.
Electrical power
Active and apparent power for single and three phase installations.
Electricity use
What an appliance costs per month and per year based on hours of use.